After completion of this assessment, you will receive a result of ‘Satisfactory’ or ‘Not Satisfactory’.
Your assessor will provide feedback via Moodle, and if you receive a ‘Not Satisfactory’ outcome, you will have the opportunity to submit additional evidence.
You are allowed one (1) opportunity to re-submit the same assessment task if required.
To achieve a ‘Satisfactory’ result:
All questions must be answered to a satisfactory standard.
You must achieve an overall mark of 60% or above.
Once all assessment tasks have been completed, you will receive a final course result of:
Competent, or
Not Yet Competent
If you are deemed ‘Not Yet Competent’ after all attempts, you will be required to re-sit the course.
To achieve a satisfactory result in this assessment:
All assessment criteria must be completed to a satisfactory standard.
Critical questions require a result of 100?fore a satisfactory outcome can be awarded.
Assessors also consider:
All parts of the assessment meet requirements set out in the course outline.
All work submitted is the student’s own work, with appropriate referencing.
Evidence is recent and reflects up-to-date knowledge.
This assessment focuses on developing practical engineering skills by integrating theoretical principles of earthing grid design with hands-on simulation and validation using ETAP software. Students will apply the IEEE 80 standard to design a safe and effective earthing system for electrical substations, with emphasis on managing hazards associated with touch and step voltages.
The project encourages critical thinking, problem solving, and the application of international standards to real-world electrical engineering scenarios. By completing this assessment, students will demonstrate their ability to design, simulate, and validate an earthing grid that complies with safety standards while improving their understanding of power system protection.
Write a report on the earthing design of the system shown in Figure 1. The report must include:
Single-phase-to-ground current calculation (Figure 1)
Earth grid design for the entire substation (Figure 2)
Touch and step potential calculations
Bonding details for all steel structures in the area
The report should be 800–1200 words (excluding references) and must answer the questions listed in Points 1–6 below.
Transformer: 1500 kVA ONAN
HV/LV = 22 / 0.433 kV
Primary Tap: -2.50%
Impedance Voltage: 6.25% on 1500 kVA
Motor (Connected to 415 V MCC @ 415 V Bus):
Motor ID: MTR_G6903
Rated Power: 220 kW
Full Load Current: 361 A
Load Factor: 1.00
Cable Information:
Cable #1: 460 m, 3C, 35 mm⊃2;, Cu XLPE/PVC
Cable #2: 48 m, 4 × 1C, 500 mm⊃2;, Cu PVC/PVC
A system study must be conducted to determine the single-phase-to-ground fault level at the 22 kV side of the 22/0.433 kV transformer (T1).
The following must be calculated and tabulated:
Single-phase-to-ground fault current at 22 kV
Single-phase-to-ground fault current at 433 V
Fault current for a 1-second clearance time
Finite Element Analysis (FEM) must be used to determine ground resistance of the earth grid.
FEM allows modelling of:
Single rods or multi-rod systems
Uniform or non-uniform soil resistivity
A two-layer soil model shall be used (refer to Figure 3):
Upper layer with finite depth h and resistivity ρ₁
Lower layer with infinite depth and resistivity ρ₂
Use IEEE 80 – Sunde’s graph (Figure 4) when performing calculations.
Determine the earth conductor size required for bonding all steel structures throughout the facility, in accordance with IEEE Std 80.
Using ETAP, simulate the earth grid layout and dimensions as shown in Figure 2.
The simulation must include:
Number of rods
Spacing between rods
Length of each rod
All results must be presented in tabulated format.
Calculate the following:
Touch voltage
Step voltage
Tolerable voltage
Note:
A concrete layer with an effective depth of 0.1 m must be included as a surface protective layer to achieve safe touch and step potentials.
Describe the requirements to ensure that:
All steel structures are properly bonded to earth
Bonding continuity is maintained throughout the system
Bonding meets safety and performance requirements
The assessment requires students to demonstrate their competence in designing, simulating, and validating an electrical substation earthing grid in accordance with IEEE 80 standards. The task involves applying theoretical knowledge and practical engineering tools specifically ETAP software to ensure safety against touch and step voltages. To achieve a satisfactory result, all criteria must be completed to the required standard, and critical questions must be answered with full accuracy.
The key components of the assessment include:
Determine fault levels at both 22 kV and 433 V transformer sides.
Calculate 1-second fault current values.
Use Finite Element Analysis (FEM) to evaluate soil resistivity and earth grid resistance.
Apply IEEE 80 Sunde’s graph for layered soil modelling.
Determine conductor size based on prospective fault levels and IEEE 80 requirements.
Model grid geometry including rods, spacing, conductor layout, and system dimensions.
Tabulate simulation results.
Include the effect of a 0.1 m concrete surface layer for safety improvement.
Explain how all steel structures will be bonded to the earthing system.
Ensure system-wide bonding integrity and compliance with safety standards.
The academic mentor supported the student with a structured, step-by-step approach to help them understand the technical requirements, apply standards accurately, and use ETAP effectively. Below is a summary of how each section was approached and explained during mentoring.
The mentor first clarified the purpose of the assessment designing a safe and compliant earthing system using engineering standards and simulation tools. The student was guided to understand:
why earthing is critical for personnel and equipment safety
how IEEE 80 defines the acceptable limits for electrical hazards
how to interpret ETAP outputs for validating safety compliance
This foundational understanding helped the student connect theory with practical engineering tasks.
The mentor explained the importance of fault current values in determining conductor sizing and grid design.
The student was shown how to extract transformer impedance values, apply base calculations, and compute single-phase-to-ground faults at both voltage levels.
Step-by-step formulas and sample calculations were demonstrated before the student attempted their own analysis.
The student produced accurate tables showing the 22 kV and 433 V fault currents and calculated the 1-second fault rating required for later steps.
The mentor explained soil resistivity concepts and how varying soil layers affect earth grid performance.
FEM was introduced as the preferred method for complex soil profiles.
The student was guided on how to reference IEEE 80 Sunde’s curves for two-layer soil adjustments and how to interpret FEM software outputs.
The student successfully modelled the upper and lower soil layers and derived the equivalent soil resistivity values required for grid simulation.
The mentor explained how conductor sizing depends on thermal capacity, fault duration, and material properties.
The IEEE 80 formula for conductor sizing was broken down into simpler terms.
The student was shown how the previously calculated fault current feeds into this step.
A compliant conductor size was selected, ensuring the earthing system could withstand the thermal effects of fault currents.
The mentor walked the student through importing grid dimensions and defining conductor mesh patterns.
They reviewed how to input rod spacing, depth, quantity, and conductor interconnections into ETAP.
The student was taught how to generate and interpret ETAP tables, including grid resistance, mesh voltage, and surface potentials.
A full ETAP simulation was completed, including tabulated results showing rod count, grid resistance, mesh and step voltages, and layout dimensions.
The mentor explained the IEEE 80 criteria for safe touch and step voltages.
They demonstrated how to calculate tolerable voltage based on worker body resistance and surface material.
The importance of the 0.1 m concrete layer was clarified, including its role in reducing surface potentials.
The student accurately calculated touch, step, and tolerable voltages and demonstrated that the grid design met safety requirements.
The mentor explained that bonding ensures equal potential across metallic structures to prevent hazardous voltages.
The student learned how to document bonding requirements for steel structures, transformer frames, panel enclosures, and cable trays.
Continuity testing and compliance documentation were also reviewed.
The student provided a comprehensive bonding strategy demonstrating that all steel structures and equipment were safely connected to the grid.
By following the structured guidance, the student successfully completed all parts of the assessment and met each requirement to a satisfactory standard. The final submission demonstrated:
A complete earthing grid design aligned with IEEE 80.
Accurate fault current calculations and soil modelling.
Selection of compliant earthing conductors.
ETAP simulation with correct interpretation of results.
Validated touch and step voltage compliance.
Thorough bonding and continuity documentation.
Application of international engineering standards (IEEE 80).
Understanding of electrical safety principles related to earthing.
Use of ETAP for engineering simulations and verification.
Integration of theoretical and practical engineering skills.
Problem-solving using real-world electrical design constraints.
Technical report writing and documentation.
Looking for clarity, structure, or guidance before starting your own assignment? Our expertly crafted sample solution is available to help you understand the assessment requirements, formatting expectations, and the level of depth needed for a strong submission. This reference sample is designed to support your learning not to be submitted as your own work.
Submitting the provided sample directly may lead to plagiarism issues and academic penalties. To keep your academic record safe, always use samples strictly for study and reference purposes.
If you need a fully original, perfectly tailored, and plagiarism-free assignment written according to your specific instructions, our professional academic writers are ready to assist. Every fresh solution is custom-written, aligned with your guidelines, and checked through plagiarism tools to ensure 100 percent originality. This helps you save time, reduce stress, and submit confidently.
Written specifically for your topic, criteria, and learning outcomes
Zero plagiarism, fully original, and safe to submit
Delivered by qualified academic experts
Proper referencing, formatting, and academic tone
Fast turnaround options available
Take the next step towards higher grades with reliable academic support.
Download Sample Solution
CTA Button: Download Sample Solution
Order Fresh Assignment
CTA Button: Order Fresh Assignment
© Copyright 2026 My Uni Papers – Student Hustle Made Hassle Free. All rights reserved.